Description
Volts 12 BCI J185
Cells 6
Terminal Type DT
Included Hardware Stainless Steel Nuts & Bolts
Size & Thread DT
Charge
Charge Voltage Range 14.7V @ 25°C (77°F)
Float Voltage Range 13.8V @ 25°C (77°F)
Recommended Charge Current Capacity (String) 45 A
Maximum Charge Current (String) 65 A
Self-Discharge Rate Less than 2% per month at 25°C (77°F)
Internal Resistance 2.3 mO
Capacity
Cold Crank Amps (CCA) 0°F / -17°C 1000
Marine Crank Amps (MCA) 32°F / 0°C 1200
Reserve Capacity (RC @ 25A) 420 Minutes
Reserve Capacity (RC @ 75A) 110 Minutes
Capacity Affect by Temperature 40°C
(104°F) 25°C
(77°F) 0°C
(32°F) -15°C
(5°F)
102% 100% 85% 65%
Hour Rate Capacity / AMP Hour Current / AMPs
@ 100 Hour Rate 240 AH 2.4 A
@ 20 Hour Rate 215 AH 10.75 A
@ 10 Hour Rate 193 AH 19.3 A
@ 5 Hour Rate 172 AH 34.4 A
Reviews